The flow monitor PPS is a flow monitor for nominal pipe sizes greater than NW 32. Fluid flow (regardless of direction) deflects the paddle and over an eccentric moves a magnet holder fitted to a permanent magnet.
The magnet actuates non-contacting a dry-reed switch embedded in the switching tube.
The paddle switch is available with N/O contact or N/C contact. The inlet and outlet pipe section should be approximately three times the nominal size of the piping.
The flow monitor can be fitted in a standard T piece or reducing pipe. Ideally the flow monitor should be fitted in horizontal piping.