Sensor Input Number of Inputs
Sensor Input Terminal Voltage
- Maximum 26 V, Min. 18 V (0 ... 22.6 mA)
Sensor Input Wiring
- 2 conductor, twisted, shielded, 0.5 ... 0.75 mm² (22 ... 18 AWG)
Sensor Input Maximum Cable Length
Sensor Input Communication
- 4 ... 20 mA
- HART protocol, for supported sensors: SITRANS LR110, LR120, SITRANS Probe LU240
Sensor Input 4 ... 20 mA Sensor Input
- Resolution 0.025 % of Full Scale
- Accuracy 0.1 % of Full Scale
Sensor Input HART Sensor Input
- Resolution and accuracy are dependent on connected sensor
Digital Input Switching Threshold, Low
Digital Input Switching Threshold, High
Digital Input Bias Voltage
Analog Output Range
- 0 ... 20 mA or 4 ... 20 mA
- Maximum load 750 ohm
- Resolution 0.1 % of Range
Analog Output Wiring
- 2 conductor, twisted, shielded, 0.5 ... 0.75 mm² (22 ... 18 AWG)
Cable Transducer and mA Output Signal
- Transducer, mA output: 2 copper conductors, twisted, with foil shield/drain wire, 300 V 0.5 … 0.75 mm² (22 … 18 AWG)
- Relay/power to be copper conductors per local requirements to meet 250 V 5 A contact rating
Relay Output Rating
- 5 A at 250 Vac, non-inductive
Installation Conditions
- Location Indoor/outdoor
- Installation category II
- Pollution Degree 4
Ambient Conditions
- Ambient temperature -20° to +50° C (-4° to +122° F)
- Storage temperature -20° to +50° C (-4° to +122° F)
Weight
- Wall Mount 1.22 kg (2.68 lb)
- Panel mount 1.35 kg (2.97 lb)
Degree of Protection
- Wall Mount IP65/Type 4X
- Panel mount IP54/Type 3
LCD Display
- 60 x 40 mm (2.36 x 1.57 inch) LCD, 240 x 160 pixels resolution
Power Supply AC Version
- 100 ... 230 Vac, ± 15 %, 50/60 Hz, 36 VA (17 W)
Certificates & Approvals
- CE
- UKCA
- RCM
- EAC
- FM
- CCSAUS
- cULus
Optional Fieldbus
- HART, with Active/Passive 4 ... 20 mA
- Modbus RTU
- PROFIBUS PA
- PROFIBUS DP
- ProfiNet