Version
- Miniature Pressure switch
- Option:
- Version for hazardous areas (Ex ia)
- Oxygen version (Cleaned for oxygen Service)
- NACE compliant per MR-0175, ISO 15156 and MR-0103
- Drying of Wetted Parts
- Offshore Version
- Tropical version (Suitable for environments with increased Air humidity)
- Geothermal Version
- Version for ammonia applications
Set Point Repeatability
- ≤ 1 % of end of setting Range
Ignition Protection Type (Option)
- Ex ia I Ma (Mines)
- Ex ia IIC T6/T4 1) Ga (Gas)
- Ex ia IIIC T85/T135 1) Da IP66 (Dust)
Safety-Related Maximum Values (Only for Ex Ia Version)
- Current li: 100 mA Internal inductance Li, 0 mH
- Power Pi 0.75 W
- Voltage Ui: DC 30 V Internal capacitance Ci, 0 μF
Contact Version
- The DPDT function is Realised with 2 simultaneously triggering SPDT micro switches. See table on next page for available Contact versions.
- 1 x DPDT (Double Pole Double Throw)
- 1 x SPDT (Single Pole Double Throw)
Electrical Connection
- Threaded Connection with Connection cable Material of Threaded Connection: Stainless Steel 316
- Threaded Connections: - 1/2” NPT Male - M20 x 1.5 Male via Adapter - 1/2” NPT Female, 3/4” NPT via Adapter
- Connection cable: - Length: 1.5 m, 3 m, 5 m (Other lengths on Request) - Cable sheath material: Silicone - Wire cross-section: 0.5 mm² (20 AWG)
- Terminal Box: - Aluminium Alloy, Copper-Free, epoxy Resin Coated - 3 x 1/2” NPT Female - Ingress Protection IP65
Dielectric Strength
- Safety ClassI (IEC 61298-2: 2008)
Process Connection
- 1/4” NPT Female (Standard)
- 1/2” NPT, G 1/4 Female via Adapter
- M20 x 1.5 Male via Adapter
- Further threaded Connections and open Connecting flanges on Request
- 1/2” NPT, G 1/2 A, G 1/4 A Male via Adapter
Permissible Temperature
- Medium: Depending on Sensor Element and Sealing, see tables on next page
- Ambient: -40° to +85° C for Non-Ex Versions.
- For Version Ex ia, see Operating instructions.
Switch Enclosure
- Tamper-proof due to access cover plate with lead Seal option
- Laser-engraved product label from Stainless Steel