SCH-DDCM Differential Pressure Switch

Brand: KOBOLD Instruments, Inc

The SCH-DDCM differential pressure monitors are suitable for monitoring and controlling differential pressures, flow monitoring and automatic checking of filter plants.

A double chamber system with stainless steel bellows resp. NBR diaphragm accurately detects the difference between the two applied pressures.

The differential pressure to be monitored is infinitely adjustable within the ranges mentioned in the summary of models.

The settings relate to the lower switching point (in the case of falling differential pressure); the upper switching point (in the case of rising differential pressure) is the value of the switching differential higher.

All differential pressure control switches can also be used in the negative pressure area. Every pressure switch has two pressure connections.

9 models matching criteria
  • Pressure Range - Non-Adjustable -0.1 to 0.4 bar
100+ In Stock
$187.00CAD
Does not ship to United States
  • Pressure Range - Non-Adjustable 10 to 60 mbar
100+ In Stock
$1,355.00CAD
Does not ship to United States
  • Pressure Range - Non-Adjustable 20 to 160 mbar
100+ In Stock
$2,358.00CAD
Does not ship to United States
  • Pressure Range - Non-Adjustable 4 to 25 mbar
100+ In Stock
$2,252.00CAD
Does not ship to United States
  • Pressure Range - Non-Adjustable 0.5 to 6 bar
50+ In Stock
$2,414.00CAD
Does not ship to United States
  • Pressure Range - Non-Adjustable 1 to 4 bar
50+ In Stock
$2,291.00CAD
Does not ship to United States
  • Pressure Range - Non-Adjustable 3 to 16 bar
50+ In Stock
$2,380.00CAD
Does not ship to United States
  • Pressure Range - Non-Adjustable 0.2 to 1.6 bar
50+ In Stock
$2,379.00CAD
Does not ship to United States
  • Pressure Range - Non-Adjustable 100 to 600 mbar
25+ In Stock
$1,352.00CAD
Does not ship to United States

Specifications

Accuracy

  • 1 bar

Ambient Temperature Range

  • -25° to 70° C (-13° to 158° F)

BSP Connection

  • G 1/4” Female

Diaphragm Material

  • NBR

Electrical Rating

  • 0.3 A at 250 Vdc Resistive
  • 5 A at 250 Vac Inductive
  • 8 A at 24 Vdc Resistive
  • 8 A at 250 Vac Resistive

Enclosure / Body Material

  • 303 Stainless Steel - Sensor Casing
  • Sea Water Resistant Aluminum Die Casting GD AI Si 12

Environmental Protection

  • IP54

Maximum System Pressure

  • bar: 0.5 to 25
  • kPa: 50 to 2,500
  • psi: 7.252 to 362.6

Mounting Position

  • Vertically Upwards

Set Point Range

  • bar: 0.04 to 16
  • kPa: 4 to 1,600
  • psi: 0.58 to 232.1

System Pressure

  • bar: 130
  • kPa: 13,000
  • psi: 1,885

Temperature Range

  • 85° C (185° F) - Max.
show more