SITRANS TH200 Temperature Transmitter
Brand: Siemens AGSITRANS TH200 is designed to support all common RTDs, thermocouples, resistance and millivolt sensors.
Setup is quick and easy with the transmitter modem and SIPROM T software.
Unique user-friendly details are implemented, one of them being the direct readout of the output current with a multimeter without having to open the 4 to 20 mA loop.
A red/green LED indicates the device status at a glance.
Transmitters of the "intrinsically safe" type of protection can be installed within potentially explosive atmospheres.
The devices meet the directive 2014/34/EU (ATEX) as well as the FM and CSA requirements.
Features- Measures temperature with a linear output signal
- High accuracy across entire ambient temperature range
- Reduces plant noise
- Alarm signal for sensor break or short-circuit according to NAMUR 43
- Electro magnetic compatibility (EMC) according to DIN EN 61326 and NE21
- Saves expensive compensation cables with its internal reference junction
- Galvanic insulation for accuracy and safety in thermocouple applications
- Single- or dual-point trim
- Custom characteristic curve for application of non-standard sensors
- Difference- and average- measurement
- Explosion protected variants for US, Canada and Europe
- Rugged design, fully potted electronics
Specifications
Brand
Output Signal
- 4-20 mA, 2-Wire
Auxiliary Power
- 11-35 Vdc
Load
- 500 ohms
Error Due to Internal Reference Junction
- < 0.5° C
Ambient Temperature
- -40° C to 85° C
- -40° F to 1855° F
Electromagnetic Compatibility
- acc. to EN 61326 and NE21
Relative Humidity
- < 98 %, with condensation
Material
- Molded Plastic
Weight
- 50 g
Degrees of Protection
- Enclosure: IP40
- Terminals: IP00
Certifications & Approvals
- PTB 05 ATEX 2040X
- II 1 G Ex ia IIC T6/T4
- II 2 (1) G Ex ia/ib IIC T6/T4
- II 3(1) G Ex ia/ic IIC T6/T4
- II 1D Ex iaD 20 T115° C
- II 3 G Ex nL IIC T6/T4
- II 3 G Ex nA IIC T6/T4
- FM 3024169
- FM 3024169C
- IS / Class I, II, III / Div. 1 / GP ABCDEFG T6, T5, T4
- EAC Ex(GOST)
- NEPSI
- IEC
- EXPO-LABS
Units of Measure
- °C
- °F
Sensor Current
- < 0.45 mA
Response Time
- < 250 milliseconds for 1 sensor with break monitoring
Sensor Type
- Pt100 (IEC) 2-Wire
- Pt100 (IEC) 3-Wire
- Pt100 (IEC) 4-Wire
- Thermocouple Type: B, C, D, E, J, K, L, N, R, S, T, U
- SITRANS TH200 transmitters can be used in all industrial sectors.